V1000 is a general purpose inverter drive covering the demands of a wide field of applications including Open-Loop-Vector functionality and the usage of PM motor without feedback

Features

  • High flux braking for 50% reduction of braking time
  • Quick response on load and speed changes to improves machine performance.
  • Online Auto-Tuning to optimise for improved motor performance at low speed
  • Open Loop Vector Control for PM motor operation.
  • Safe Disable Inputs for Safe Torque OFF
 

Normal Duty Applications

Heavy Duty Applications

Compact Vector control Drive Ratings:

  • 200V:
    > 1Ph: 0.1 to 2.2 kW
    > 3Ph: 0.1 to 15kW
  • 400V:
    > 3Ph: 0.2 to 15kW

Download

Download catalogue

 

 

 

200V Single Phase

V1000 Model number PND(kW) IND(A) PHD(kW) IHD(A)
CIMR-VTBA0001BAA 0.2 1.2 0.1 0.8
CIMR-VTBA0002BAA 0.4 1.9 0.2 1.6
CIMR-VTBA0003BAA 0.75 3.3 0.4 3.0
CIMR-VTBA0006BAA 1.1 6.0 0.75 5.0
CIMR-VTBA0010BAA 2.2 9.6 1.5 8.0
CIMR-VTBA0012BAA 3 12 2.2 11

200V Three Phase

V1000 Model number PND(kW) IND(A) PHD(kW) IHD(A)
CIMR-VT2A0001BAA 0.2 1.2 0.1 0.8
CIMR-VT2A0002BAA 0.4 1.9 0.2 1.6
CIMR-VT2A0004BAA 0.75 3.5 0.4 3
CIMR-VT2A0006BAA 1.1 6 0.75 5
CIMR-VT2A0010BAA 2.2 9.6 1.5 8
CIMR-VT2A0012BAA 3 12 2.2 11
CIMR-VT2A0020BAA 5.5 19.6 3.7 17.5
CIMR-VT2A0030FAA 7.5 30 5.5 25
CIMR-VT2A0040FAA 11 40 7.5 33
CIMR-VT2A0056FAA 15 56 11 47
CIMR-VT2A0069FAA 18.5 69 15 60

400V Single Phase

V1000 Model number PND(kW) IND(A) PHD(kW) IHD(A)
CIMR-VT4A0001BAA 0.4 1.2 0.2 1.2
CIMR-VT4A0002BAA 0.75 2.1 0.4 1.8
CIMR-VT4A0004BAA 1.5 4.1 0.75 3.4
CIMR-VT4A0005BAA 2.2 5.4 1.5 4.8
CIMR-VT4A0007BAA 3 6.9 2.2 5.5
CIMR-VT4A0009BAA 3.7 8.8 3 7.2
CIMR-VT4A0011BAA 5.5 11.1 3.7 9.2
CIMR-VT4A0018FAA 7.5 17.5 5.5 14.8
CIMR-VT4A0023FAA 11 23 7.5 18
CIMR-VT4A0031FAA 15 31 11 24
CIMR-VT4A0038FAA 18.5 38 15 31
Control Characteristics
Product V1000
Type Compact Vector Control Drive
Rated Output Voltage (dependent on input) Three Ph 200V Class : 200 to 240VAC
Three Ph 400V Class : 380 to 480VAC
Single Ph 200V Class : 200 to 240VAC
Motor Types Induction Motor, Permanent Magnet Motor (IPM/SPM)
Control Methods Open Loop Vector Control (Current Vector), V/f Control, PM Open Loop Vector Control (for SPM and IPM motors)
Speed Control Range 1:100 (Open Loop Vector Control), 1:20 to 40 (V/f Control), 1:10 (PM Open Loop Vector Control)
Starting Torque 200% / 0.5 Hz (assumes Heavy Duty rating IM of 3.7 kW or less using Open Loop Vector Control),
50% / 6 Hz (assumes PM Open Loop Vector Control)
Frequency Range 0 to 400Hz
Frequency Accuracy Digital reference: within ±0.01% of the max. output frequency (-10°C to +50°C)
Analog reference: within ±0.1% of the max. output frequency (25°C±10°C)
Frequency Setting Resolution Main frequency reference: 0 to 10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
Main speed reference : Pulse Train Input (max. 32 kHz)
Output Frequency
Resolution
20 bit of maximum output frequency (parameter E1-04 setting)
Torque Limit Open Loop Vector Control allows separate settings in four quadrants
Accel/Decel time 0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Environmental Factors
Ambient Temperature −10 to +50˚C (open chassis), −10 to +40˚C (enclosure)
Altitude Up to 1000 meters
Humidity 95 RH% or less (no condensation)
Shock 10 to less than 20 Hz (9.8 m/s2) max., 20 to 55 Hz (5.9 m/s2) max.
Area of Use Indoors
Protection Features 
Motor Protection Motor overheat protection based on output current
Momentary Overcurrent
Protection
Drive stops when output current exceeds 200% of Heavy Duty Rating
Overload Protection Drive stops after 60 s at 150% of rated output current (Heavy Duty Rating)
Overvoltage Protection 200 V class: Stops when DC bus exceeds approx. 410 V
400 V class: Stops when DC bus exceeds approx. 820 V (approx. 740 V when power supply voltage is less than 400 V)
Undervoltage Protection Three-phase 200 V class: Stops when DC bus falls below approx. 190 V
Single-phase 200 V class: Stops when DC bus falls below approx. 160 V
Three-phase 400 V class: Stops when DC bus falls below approx. 380 V (approx. 350 V when the power supply voltage is less than 400 V)
Momentary Power Loss
Ride-Thru
Stops after approx. 15 ms (default). Parameter settings allow the drive to continue running if power loss lasts for up to approx. 2 s 
Heatsink Overheat
Protection
Thermistor
Stall Prevention Separate settings allowed during acceleration, and during run. Enable/disable only during deceleration.
Ground Fault Protection Protection by electronic circuit
Charge LED Charge LED remains lit until DC bus has fallen below approx. 50 V
Standards Compliance UL508C
IEC/EN61800-3,IEC/EN61800-5-1
ISO/EN13849-1 Cat.3 PLd,IEC/EN61508 SIL2
Power Specifications
Rated input Voltage/Frequency Three-phase AC power supply 380 to 480 V 50/60 Hz ; DC power supply: 510 to 680 V
Three-phase AC power supply 200 to 240 V 50/60 Hz ; DC power supply: 270 to 340 V
Single-phase AC power supply 200 to 240 V 50/60 Hz ; DC power supply: 270 to 340 V 
Allowable Voltage
Fluctuation
−15% to 10%
Allowable Frequency
Fluctuation
±5%
Common Specifications
Carrier Frequency 2 kHz (user-set, 2 to 15 kHz possible)
Multi Funcction Digital Inputs 7 Digital Inputs ( NPN or PNP ) , 24VDC. 
Multi Function Digital Outputs P1,P2 – PC Photocoupler Output (48 Vdc (or less), 50 mA (or less)) and
1 fault relay MA-MB-MC (Digital output 30 Vdc (or less), 10 mA to 1 A ,250 Vac (or less), 10 mA to 1 A)
Multi Function Analog Inputs 2 Multi function Analog input A1 (0 to 10 Vdc (20 kΩ) resolution: 1/1000) &  A2  ( 0 to 10 Vdc (20 kΩ) resolution: 1/1000, 4 to 20 mA or 0 to 20 mA (250 Ω) resolution: 1/500)
Multi Function Analog Output 1 Multi function Analog outputs  AM-AC (0 to 10 Vdc (2 mA or less)Resolution: 1/1000))
Pulse Train  1 Pusle Train output (0.5 to 32 kHz)
1 Pulse Train input (max 32 kHz)
Programming Interface Serial port or USB B port in front of VFD
Serial communication MEMOBUS/Modbus (RTU mode) comm. RS-485, Max. 115.2 kbps
Optional communication Protocols MECHATROLINK-II,MECHATROLINK-III,CC-Link, DeviceNet, CompoNet, PROFIBUS-DP , CANopen , EtherCAT,EtherNet/IP, Modbus/TCP
Additional Functions Momentary power loss ride-thru, Speed search, Overtorque detection, Torque limit, 17-step speed (max),Accel/decel time switch, S-curve accel/decel, 3-wire sequence, Auto-tuning (rotational, stationary tuningfor resistance between lines), Dwell, Cooling fan on/off switch, Slip compensation, Torque compensation,Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop,Overexcitation braking, High slip braking, PID control (with sleep function), Energy saving control, MEMOBUS comm. (RS-485/422 max, 115.2 kbps), Fault restart, Application presets, DriveWorksEZ (customized function),Removable terminal block with parameter backup function.

V1000 solar drive is used for solar pump applications

  • Suitable for BLDC and PM motor
  • Suitable for surface mount and submersible pump for 3 Phase 200Volts/400volts induction motor
  • wide range capacity from 0.1kW to 18.5kW
  • All day run stop restart mode management
  • Diagnostics and self protection features.
  • Protection against dry run of pump
  • Simple and faster installation and commissioning.

Download

Download catalogue

Compact Vector control Drive Ratings:

  • 200V:
    > 1Ph: 0.1 to 2.2 kW
    > 3Ph: 0.1 to 15kW
  • 400V:
    > 3Ph: 0.2 to 15kW
  V1000 Solar Technical Electrical specification
Pump inverter type V/F control with derived MPPT Technology
Dual supply ( Grid/ Solar) Change over Available
input DC voltage ( VOC) 400volts DC for 200volts Class and 800volts class for 400 volts drive
input DC voltage ( Vmp) 280 VDC tp 310 V Dc /510 V dc to 620 V DC
Input DC cuttent and power As per motor capacity
Min frequency 0hz selectable setting range
Max frequency 120Hz
Shock 10 to less than 20 Hz (9.8m/s2) max
output Ac voltage 3 phase 190-240v (-15%.+10%)/380-480V/(-15%,+10%)
Output Ac voltage As per chart above
Motor frequency 0-60Hz
Motor control technology V/f Control
MPPT voltage 230V to 360 V for 200 volts

 

460V to 620 V for 400 volts

Over load capacity 120% for ND
Under voltage 125V DC for 200 volts Class/ 250 for 400 volts Class
Protection Dry run , short circuit, Open Phase in input & output side, High Voltage, Low voltage and over load , earthing, recerse polarity.
Ambient temp -10deg to 50 deg
Relative humidity Max 95% relative humanity